1. Motivation

The pool pump is the largest power consumer in a swimming pool. At the same time, it determines water quality. The required circulation volume strongly depends on water temperature:

Water TemperatureRiskRecommended Circulation
> 26 °CHigh algae growth, turbidityMaximum (8–12 h/day)
20–26 °CNormal operationStandard (4–8 h/day)
< 20 °CMinimal algae growthMinimal (1–4 h/day)

A fixed timer is either oversized (wasting power in cold weather) or undersized (poor water quality during heat waves).

Goal: Automatically adjust daily pump runtime based on measured pool temperature.

2. Concept

The timer-configured runtime is dynamically extended when water temperature exceeds a threshold. The extension is proportional to the temperature difference.

Formula

effectiveRuntime = baseRuntime + max(0, (poolTemp - tempCircThreshold) × tempCircFactor)
effectiveRuntime = min(effectiveRuntime, tempCircMaxRuntime)

Parameters

ParameterTypeDefaultRangeDescription
tempCircThresholddouble24.0 °C0–40 °CTemperature above which runtime is extended
tempCircFactoruint16_t30 min/°C0–120 min/°CExtra minutes per °C above threshold
tempCircMaxRuntimeuint16_t720 min60–1440 minAbsolute upper limit for total runtime

Computed Fields (read-only)

FieldDescription
effectiveRuntimeCalculated runtime in minutes (for status/logging)
effectiveEndTimeResulting switch-off time

Behavior During Temperature Changes

The calculation runs continuously (every loop()), but the end time may only move later. Once the pump is running, the highest calculated end time is remembered.

Start (10:00, 24 °C):   end = 10:00 + 480 min = 18:00
14:00, 28 °C → +4×30:   newEnd = max(18:00, 20:00) = 20:00 ✓
16:00, 26 °C → +2×30:   newEnd = max(20:00, 19:00) = 20:00 ⛔ stays

Rule: The pump switches off no earlier than the original timer end time — even if it cools down later. This prevents surprise shutoffs and erratic behavior.

// Core logic in RuleTimer/RuleAuto::loop():
uint16_t newEndMinutes = calculateEffectiveEndMinutes(
    baseStartMinutes, baseEndMinutes, poolTemp);

// Only extend, never shorten:
if (newEndMinutes > activeEndMinutes) {
    activeEndMinutes = newEndMinutes;
}

3. Examples

Summer (Pool 30 °C / 86 °F)

Timer:         10:00 – 18:00  (base = 480 min)
Threshold:     24 °C
Difference:    6 °C
Extension:     6 × 30 = 180 min
Effective:     480 + 180 = 660 min
Switch-off:    10:00 + 660 min = 21:00

→ Pump runs 3 hours longer. More circulation during heat prevents algae.

Mild (Pool 22 °C / 72 °F)

Timer:         10:00 – 18:00
Threshold:     24 °C
Difference:    22 < 24 → No extension
Effective:     = base = 480 min
Switch-off:    18:00

→ Normal runtime, no change.

Hot (Pool 34 °C, max runtime reached)

Timer:         10:00 – 18:00
Difference:    10 °C
Extension:     10 × 30 = 300 min
Subtotal:      480 + 300 = 780 min
Max runtime:   720 min (12 h)
Effective:     min(780, 720) = 720 min
Switch-off:    10:00 + 720 min = 22:00

→ The upper limit prevents excessive pump wear.

4. System Integration

Affected Components

ConfigManager (ControllerSettings)
  + tempCircThreshold: double
  + tempCircFactor: uint16_t
  + tempCircMaxRuntime: uint16_t

RuleTimer / RuleAuto
  + calculateEffectiveRuntime()  — shared helper
  + uses calculated runtime instead of fixed end time

MqttPublisher
  + 3 new Number entities via HA Discovery
  + Command handlers for /temp-circ-*/set

WebPortal (later)
  + Input fields in Config tab

Core Logic

uint16_t calculateEffectiveRuntime(uint16_t baseMinutes, float poolTemp) {
    auto &s = ConfigManager::getSettings();

    // NaN or below threshold: use base runtime
    if (poolTemp != poolTemp || poolTemp <= s.tempCircThreshold) {
        return baseMinutes;
    }

    float diff = poolTemp - s.tempCircThreshold;
    float extraMinutes = diff * s.tempCircFactor;

    // Round to whole minutes
    uint16_t extra = static_cast<uint16_t>(extraMinutes + 0.5f);
    uint16_t total = baseMinutes + extra;

    // Apply upper limit
    return (total > s.tempCircMaxRuntime) ? s.tempCircMaxRuntime : total;
}

Midnight Crossing

The timer logic in checkPoolPumpTimer() already supports end times that cross midnight (e.g. start 22:00, end 02:00). The temperature-based extension can use the same mechanism — the effective end time is not capped at 24:00.

NVS Persistence

The 3 parameters are stored in the ControllerSettings struct via NVS. They are configuration values (rarely changed), so wear is not a concern.

5. Home Assistant Integration

Each parameter is published as a Number entity via HA Discovery:

EntityTopic SuffixMinMaxStep
temp-circ-threshold/number/pool-controller/temp-circ-threshold/…0400.5
temp-circ-factor/number/pool-controller/temp-circ-factor/…01205
temp-circ-max-runtime/number/pool-controller/temp-circ-max-runtime/…60144015

Plus a sensor for computed effective runtime:

EntityTopic SuffixUnit
effective-runtime/sensor/pool-controller/effective-runtime/…s

6. Implementation Plan

StepFile(s)Effort
1. Extend Config structConfigManager.hpp~10 min
2. Helper function + defaultsTimer.hpp, Timer.cpp~15 min
3. Modify RuleTimer::loop()RuleTimer.cpp~20 min
4. Modify RuleAuto::loop()RuleAuto.cpp~10 min
5. MQTT Discovery + handlersMqttPublisher.cpp~30 min
6. Build + Test~10 min
Total~1.5 h

7. User Guide

7.1 Quick Start

  1. Set a timer — temperature-based circulation only works in Timer or Auto mode with a configured time window. Set your desired base runtime first (e.g. 10:00–18:00).
  2. Set a threshold — start with 24 °C. Below this temperature, the pump runs the normal timer schedule.
  3. Set a factor — start with 30 min/°C. Every degree above threshold adds half an hour.
  4. Set a max runtime — start with 720 min (12 h). Prevents excessive runtime on very hot days.

That’s it — the pump will now run longer when the water is warm.

Rule of thumb: Once configured, the feature works automatically. No manual intervention needed. You can watch the Circ. Runtime value on the dashboard to see the calculated extension at a glance.

7.2 Recommended Settings by Pool Type

Find your setup and use these as a starting point:

Pool TypeThresholdFactorMax RuntimeWhy
☀️ Small above-ground (≤15 m³)22 °C20 min/°C480 min (8 h)Smaller volume needs less margin
🏊 Medium family pool (25–50 m³)24 °C30 min/°C720 min (12 h)Good balance of water quality and cost
🌴 Large pool / high bather load (50+ m³)22 °C40 min/°C960 min (16 h)More circulation needed for hygiene
🌡️ Heated pool26 °C15 min/°C600 min (10 h)Already filtered more via heating pump

If you have solar heating, keep the threshold at or above your solar minimum temperature to avoid overlap.

7.3 Configuration via Web UI

Pool Tab

Open the settings menu (gear icon) → Pool🌡️ Temperature-Based Circulation section.

FieldDescription
Circ. Temp ThresholdPool temperature must exceed this value for extension to apply.
Circ. Temp FactorHow many extra minutes per °C above threshold. Higher = more aggressive extension.
Circ. Max RuntimeThe absolute maximum pump runtime per day, including any extension.

Click Save Pool Settings at the bottom of the tab.

Dashboard Telemetry

On the main dashboard, the bottom strip shows Circ. Runtime — the currently calculated effective runtime in minutes. This number updates live as the pool temperature changes and the only-extend rule tracks the highest computed value.

7.4 Configuration via Home Assistant

Once connected via MQTT, three Number entities appear in Home Assistant:

EntityPurpose
number.pool_controller_temp_circ_thresholdSet the temperature threshold
number.pool_controller_temp_circ_factorAdjust the extension factor
number.pool_controller_temp_circ_max_runtimeSet the upper runtime limit
sensor.pool_controller_effective_runtimeRead-only — shows computed runtime

You can change values from the Home Assistant UI, automations, or dashboards. Changes take effect immediately — no reboot required.

7.5 Example: Automating with Home Assistant

Scenario: Adjust factor based on weather forecast.

automation:
  - alias: "Aggressive circulation on hot days"
    trigger:
      platform: numeric_state
      entity_id: weather.home
      attribute: temperature
      above: 32
    action:
      service: number.set_value
      target:
        entity_id: number.pool_controller_temp_circ_factor
      data:
        value: 45

Scenario: Notify when circulation ran near max.

automation:
  - alias: "High circulation alert"
    trigger:
      platform: numeric_state
      entity_id: sensor.pool_controller_effective_runtime
      above: 700
    action:
      service: notify.mobile_app_phone
      data:
        message: "Pool circulation running near max ({{ states('sensor.pool_controller_effective_runtime') }} min)"

7.6 FAQ / Troubleshooting

Q: The pump runs much longer than expected — why?

Check your pool temperature. If it’s above the threshold and the factor is high, long runtimes are normal. Look at the Circ. Runtime value to see the calculated extension. Lower the factor or raise the threshold if needed.

Q: The pump stopped earlier than I expected — why?

The extension only applies while the pump is running. If the pump was already on, the end time may have been extended earlier but then cooled down — the only-extend rule preserves the highest end time. Check that:

  1. The pool temperature is actually above the threshold
  2. The timer window is configured (temperature extension doesn’t activate the pump by itself)

Q: Can the pump start earlier than the timer start?

No. The feature only extends the end time. The start time remains exactly as configured in the timer. (See only-extend rule in §2.)

Q: Does the max runtime reset each day?

Yes. At the start of each timer cycle, the effective end time resets to the base timer end. The extension is recalculated fresh.

Q: I changed values in the Web UI but nothing happened — why?

Check the Mode on the dashboard. Temperature-based circulation works in Timer and Auto modes. In Manual or Boost mode, the feature is inactive.

Q: Will this wear out my pump faster?

The tempCircMaxRuntime parameter is specifically designed to prevent excessive runtime. Set it to a value your pump can handle — 12 hours/day is safe for most pool pumps. Consult your pump’s duty cycle specification.

8. Future Extensions (v2)

  • Cold reduction: Optional tempCircMinRuntime below a lower threshold
  • Trend-based: Factor in whether temperature is rising or falling
  • Seasonal calendar: Automatically adjust base parameters for summer/winter